Socomec SLBM Load Break Switch kit, Base/DIN Rail mount, w/ Direct Handle, 3P 100A

Item No. SLBM1003PD
Product Range: SLBM
Component Type (ETIM Class)
Switch disconnector
Electrical
Rated permanent current at AC-21, 400 V100 A
Rated permanent current Iu100 A
Number of poles3
Rated operation power at AC-23, 400 V100 kW
Rated operation current Ie at AC-23a, 400 V100 A
Rated operation current Ie at AC-23a, 500 V80 A
Rated operation current Ie at AC-23a, 690 V63 A
Rated short-time withstand current lcw5 kA
Rated insulation voltage Ui800 V
Construction
Degree of protection (IP), front sideIP65
Version as main switchYes
Version as reversing switchNo
Number of switches1
Suitable for floor mountingNo
Suitable for front mounting 4-holeNo
Suitable for front mounting centreNo
Suitable for distribution board installationYes
Suitable for intermediate mountingNo
Mechanical
Padlock lockingYes
Dimensions
Height131.4 mm
Width78 mm
Depth75 mm
Weight0.7 kg
Conductor cross section solid (solid, stranded)10-70 mm²
Connectable conductor cross section10-70 mm²