Search

Socomec

Socomec SLBM Load Break Switch Body, Base/DIN Rail mount, 3P 25A

Item No. 22003002
Product Range: SLBM
Component Type (ETIM Class)
Switch disconnector
Electrical
Rated operating voltage Ue400690 V
Max. rated operation voltage Ue AC800 V
Rated permanent current at AC-21, 400 V25 A
Rated permanent current Iu25 A
Number of poles3
Rated operation power at AC-23, 400 V11 kW
Rated short-time withstand current lcw1.26 kA
Type of control elementOther
Type of electrical connection of main circuitScrew connection
Construction
Device constructionBuilt-in device fixed built-in technique
Colour control elementOther
Degree of protection (IP), front sideIP20
Version as main switchYes
Version as maintenance-/service switchYes
Version as safety switchYes
Version as emergency stop installationYes
Version as reversing switchNo
Number of switches1
Mechanical
Mechanical life (service cycles)10000 cycles
Dimensions
Height68 mm
Width45 mm
Depth64 mm
Connectable conductor cross section2.5-25 mm²