Branch Circuit Monitoring
NHP’s branch monitoring solution connects directly to the load side of circuit breakers for simultaneous monitoring of numerous single and/or three-phase loads. Its compact size and ability to monitor up to 96 channels with its respective split core current sensor TCD12 makes it ideal for high-density monitoring within a Power Distribution Unit (PDU).
Features and Benefits
- Compact size meter and CTs to fit in panelboards
- Easy to connect CTs scalable to monitor and analyse any combination of single-phase, two-phase, and three-phase loads for a maximum of 96 channels, up to 32A per channel
- Capability to monitor locally or remote with free to download UCS software
- Options for Modbus RTU or TCP
- View up to six different energy tariffs
- Up to 16 alarm management
WM50
Branch circuit monitoring solution
Connection type:Connect up to 8x 12-channel CTs (TCD12) | System Variables:kWh,kVArh,V,A,VA/W/Var,PF,Hz,THD (32nd harmonic), K-factor, phase-sequence |
Active energy accuracy/IEC 62053-21:Class 0.5S (mains), Class 2 for individual channels | Four Quadrant Monitoring:Yes |
Comms Enabled:Yes (Ethernet TCP or Modbus RTU) | Other I/O:Various configurations available through add-on modules, including digital I/O and analogue and temperature inputs |
Additional Features:Up to 16 internal alarms available, event and datalogging with onboard memory | |