Search

Socomec

Socomec VLB Visual Load Break Switch Kit, w/ External Handle, 6P 315A

Item No. VLB3156P
Product Range: VLB
Component Type (ETIM Class)
Switch disconnector
Electrical
Rated permanent current at AC-21, 400 V315 A
Rated permanent current Iu315 A
Number of poles6
Rated operation power at AC-23, 400 V315 kW
Rated operation current Ie at AC-23a, 400 V315 A
Rated operation current Ie at AC-23a, 500 V250 A
Rated operation current Ie at AC-23a, 690 V250 A
Rated short-time withstand current lcw17 kA
Rated insulation voltage Ui800 V
Dimensions
Width324 mm
Depth95 mm
Height195 mm